Resistance thermometer MiniTherm with threaded connection

Type series GA2700

  • EX
  • SIL2
Resistance thermometer MiniTherm with threaded connection - GA2700

Features

  • Resistance thermometer for invasive temperature measurement in tanks and pipes
  • Pt100 directly integrated into a thermowell
  • Compact design
  • High measurement accuracy
  • Fast response
  • Measuring resistor Pt100, class A
  • Circular connector M12

Options

  • Explosion protection
  • Classification per SIL2
  • Material certificate per EN 10204-3.1
  • Calibration certificate per EN 10204-3.1
  • Output signal 4...20 mA via transmitter PA2430
  • Output signal IO-Link V1.1 via transmitter PA2530
  • Thermowell with reduced tip Ø 4 mm

Technical Data

Constructional design
Design: Pt100 directly integrated into a thermowell, various types of process connections are available
El. connection: Circular connector M12
Further electrical connections upon request.
Working pressure: max. 40 bar
Measuring insert
Design: Thermowell Ø 6 mm
Option: Thermowell with reduced tip Ø 4 mm Length see order code.
Measuring resistor: - Pt100 per EN 60751, class A 3-wire
- Pt100 per EN 60751, class A 4-wire (3-wire bridged)
Degree of protection per EN 60529: IP 67
Transmitter
Installation variants: - Transmitter, Type PA 2430, for circular connector M12
- Transmitter, Type PA 2530 IO-Link, for circular connector M12
- Transmitter head mounted, Type se-ries PA210., 4…20 mA, programmable
- Transmitter head mounted, Type se-ries PA220., electrically isolated, clas-sification per SIL 2
- Transmitter head mounted, Type se-ries PA230., electrically isolated, clas-sification per SIL 2, HART
Temperature ranges
Ambient:1 -40…85 °C
Media: -50…200 °C
Storage:1 -40…85 °C
1 Different temperature ranges for devices with transmitter (see data sheets for the types PA2430 or PA2530).
Accuracy s
Pt100: Per EN 60751, class A
Response time: Per EN 60751, test procedure with flowing water (without transmitter)
Thermowell Ø 6 mm: T90 = 5.5 s
Thermowell with reduced tip Ø 4 mm: T90 = 4.5 s
Output signal transmitter
Output signal 4...20 mA : Detailed informations about transmitter type PA2430 see product page on www.labom.com.
Output signal IO-Link V1.1: Detailed informations about transmitter type PA2430 see product page on www.labom.com.
Process connection
Design: See order code
Material wetted parts
Material: Stainless steel mat.-no. 1.4404 (316L)
Tests and certificates
See documents
Type series
GA2700, GA2701

Documents

Name
Description
EN
DE
  • T4-014

    Data Sheet

  • BA_053

    Operating Instructions

  • XA_001

    Ex Instructions

  • ZER_023

    Certificate - ATEX

  • ZER_034

    Certificate - EHEDG

  • HE_087

    Manufacturer Declaration - SIL2

  • KE_011

    Declaration of Conformity