Pressure transmitter PASCAL CV for diaphragm seal operation, hygienic

Type series CV3110

  • EX
  • SIL2
  • HART
  • PROFIBUS
  • EHEDG
Pressure transmitter PASCAL CV for diaphragm seal operation, hygienic - CV3110

Features

  • Modular pressure transmitter Output signal: 4…20 mA,HART® protocol (rev. 6), option, PROFIBUS PA, option
  • Function modules:Multifunctional display with 5-segment digital display and bar graph, Switching module with 2 floating channels, maximum 0.5 A switching current, electrically isolated at all sides, without additional auxiliary power
  • Function module replacement on site without recalibration "plug and measure"
  • Hygienic design according to EHEDG, FDA and GMP recommendations
  • Material and surface quality according to the hygienic requirements
  • Limits of measuring range 0...80 mbar to 0...40 bar
  • Accuracy ≤ 0.15 %
  • Turndown 5:1
  • Degree of protection IP 66, piezoresistive measuring cell directly aerated

Options

  • Explosion protection for gases and dust
  • Certificate of measuring equipment for Russian Federation
  • Material certificate as per EN 10204-3.1
  • Calibration certificate as per EN 10204-3.1
  • Classification per SIL2
  • Hygienic design
  • EAC declaration (upon request)

Technical Data

Constructional design / case
Design: Two-chamber case design with screw cap.
  Minimum case volume, excellent moisture and condensate protection
Material: Stainless steel mat.-no. 1.4301 (304)
Degree of protection per EN 60529: - IP 66
- optional: IP 69K
Climatic category per EN 60721 3-4: 4K4H
Pressure compensation: PTFE filter system
Window: Non splintering plastic: Makrolon
Case seal: O-ring: NBR
El. connection: Screw terminal 1 mm²
Cable gland: Cable gland M16,
material: PA
  Circular connector M12
  Further cable glands upon request.
Weight: Standard device without diaphragm seal and function modules approx. 0.65 kg
Process connection
Design: See order details
Material wetted parts
Material: Stainless steel mat. no. 1.4435 316L/316
Gasket: EPDM-FDA listed (in case of flush mounted diaphragm with O-ring)
Measuring system
Sensor: Piezoresistive measuring element
System filling: Synthetic oil, free of silicon FD1, FDA listed
Hygienic design
The surface roughness of the wetted parts made of stain-less steel are executed according to EHEDG Doc.8 and ASME BPE SF3.
In case of choosing the additional feature HY, we guarantee the following surface roughness values:
Diaphragm foil: Ra ≤ 0.38 µm
Laser welds: Ra ≤ 0.76 µm
Turned parts: Ra ≤ 0.76 µm
Further versions of hygienic design upon request.
Accuracy
General: Limit point setting: per DIN 16086
  Reference conditions: per EN 60770-1
  Linearity errors: ≤ 0.15 % of span
TD 5:1 no modification
  Hysteresis: ≤ 0.05 % of nominal range
  Repeatability: ≤ 0.05 % of nominal range
  Calibration position: Vertical mounting position
  Influence of mounting position: ≤ 3.5 mbar
  Long-term drift (EN 60770-1): ≤ 0.1 % / year of nominal range
Temperature effect: Case:  
  Lower range value / upper range value  
  Range 0…60 °C: ± 0.15 % / 10K of nominal range
  Range < 0 °C, > 60 °C: ± 0.2 % / 10K of nominal range
  Process connection:
(depending on design)
 
  Diaphragm seal:
DN 25/1“
DN 32/1 1/2“
DN 40
DN 50/2“
HYGIENIC G1A
Zero point error:
4.8 mbar/10K
2.3 mbar/10K
1.6 mbar/10K
0.6 mbar/10K
1 mbar/10K
The specify zero error for the process connection is a guide value for a standard design. We can provide a detailed system calculation upon request. Systems with reduced diaphragm seal errors are also available.
Output
General: Delay time: approx. 160 ms
  Measuring cycle: 6 measurements / second
  Measuring range setting: Turndown 5:1
Basic module: 4…20 mA Signal: 4…20 mA, 2-wire
  Current range: 3.8…20.8 mA
  Current limitation: approx. 22 mA
  Alarm state: < 3.6 mA, optional > 21 mA
  Damping: 0…120 seconds
  Load RB: RB ≤ (UV-12V DC)/0,022A [Ohm]
(UV = supply voltage)
Basic module: PROFIBUS PA Signal: digital per IEC 61158-2
  Protocol: EN 50170-PROFIBUS PA, Profile 3.0
  Sensor address: 0…126 (126 = factory setting)
  Power consumption: constantly 11 mA
  Fault current IFDE : 2 mA
  Damping: 0…300 seconds
  Parameterization: SIMATIC PDM
Supply voltage
Basic module: 4…20 mA PROFIBUS PA
Standard design:    
Functional range: 12…40 V DC 9…32 V DC
Ex-design:    
Functional range: 12…30 V DC 9...17.5 V DC
Temperature ranges
Ambient: -20…85 °C
Media: depending on design, see order code
Storage: -40…85 °C
(Note safety values as per examination certificate!)
Tests and certificates
See documents
* Devices with cable gland or switching outputs might suffer from a short-time measuring deviation in case of strong electromagnetic fields (EN 61000-4-3).
Type series
CV3110, CV3111

Documents

Name
Description
EN
DE
  • D4-017-22

    Data Sheet

  • BA_028

    Operating Instruction - Basic Module

  • BA_029

    Operating Instruction - Switching Module

  • BA_030

    Operating Instruction - Display Module

  • BA_031

    Operating Instruction - Display-Switching Module

  • BA_043

    Operating Instruction - PROFIBUS PA

  • BA_044

    Operating Instruction - PROFIBUS PA without Display

  • BA_055

    Operating Instruction - HART

  • BA_081

    Operating Instruction - Display and HART

  • XA_015

    Ex Instructions

  • ZER_013

    Certificate - ATEX

  • ZER_041

    Certificate - HART

  • ZER_042

    Certificate - PROFIBUS PA

  • ZER_044

    Certificate - SIL2

  • HE_075

    Manufacturer Declaration - SIL2

  • KE_028

    Declaration of Conformity

  • Software

    PASCAL CV HART (DD/EDD) for Simatic PDM V6.0 SP5, V8.1 and V9.x

  • Software

    PASCAL CV Profibus PA (DD/EDD) for Simatic PDM V6.0 SP5

  • Software

    PASCAL CV HART (DD/EDD) for Emerson AMS V6.1 and V8.1

  • Software

    PASCAL CV HART (DD/EDD) for Emerson Handheld Communicator 375/475