Pressure transmitter PASCAL Ci4 for diaphragm seal operation, hygienic

Type series CI4110

  • EX
  • SIL2
  • HART
  • EHEDG
Pressure transmitter PASCAL Ci4 for diaphragm seal operation, hygienic - CI4110

Features

  • Pressure transmitter for the measuring of relative and absolute pressures of gases, vapors and liquids in applications for food and pharmaceutical industry
  • Stainless steel case in hygienic design, degree of protection IP 65/67
  • Accuracy ≤ 0.1 %
  • High-resolution graphic display with Intuitive 4-button operation and backlight
  • Comprehensive parameterising functions
  • Comprehensive simulation and diagnostic functions
  • Quick access to device data
  • Development according to SIL2
  • Nominal range 0.25 bar to 40 bar
  • Turndown up to100:1
  • Measuring rate up to 100 Hz
  • Output signal 4…20 mA with HART® protocol
  • Configuration memory
  • Digital communication via PDM, FDT/DTM, 375/475 Field Communicator
  • Output functions: linear, invers, square root, table function with up to 64 support points
  • Media temperature up to 160 °C
  • Wetted parts stainless steel
  • Case design process connection bottom
  • Case design process connection back
  • Various hygienic process connections, selected connec-tions with EHEDG certificate
  • Approved according to NAMUR 95

Options

  • Accuracy ≤ 0.075 %
  • Explosion protection for gases and dust
  • Classification per SIL2
  • Certificate of measuring equipment for Russian Federation
  • Material certificate per EN 10204
  • Calibration certificate per EN 10204
  • Active temperature compensation (ATC technology)
  • Operating software LAB4Level for level measurements
  • Removable display and control unit
  • Degree of protection IP 69K
  • Wetted parts electropolished
  • EAC declaration (upon request)

Technical Data

Measuring ranges
See data sheet
Constructional design / case
Design: Two-chamber case, continuously rotatable by ± 170°
Case surface blasted
Material case: - Stainless steel mat.no. 1.4301/1.4305 (304/303)
- Stainless steel mat.no. 1.4404 (316L)
Material front cover: - Polypropylene, black
- Stainless steel mat.no. 1.4305 (303)
- Stainless steel mat.no. 1.4404 (316L)
Gaskets: Silicone / NBR
Degree of protection per EN 60529: - IP 65 / IP 67
- IP 69K
Climatic category per EN 60721 3-4: 4K4H
Vibration resistance per EN 61298-3: 10…60 Hz: ± 0.35 mm
60…1000 Hz: 5 g
Material window: - Macrolon
- Non splintering glass (requires front cover of stainless steel)
Elec. connection: - Circular connector M12
- Cable gland M16x1.5, PA black
- Cable gland M16x1.5, stainless steel
- Cable gland M20x1.5, PA black
- Cable gland M20x1.5, stainless steel
- 1/2" NPT, PA black
  Further connections upon request
Terminal blocks: - Spring clamp terminals up to 1.5 mm2
- Pole terminals up to 2.5 mm2
- Screwed terminals up to 2.5 mm2
Weight: approx. 1.4 kg (without diaphragm seal)
Type plate: Laser marking
Process connection
Position: - bottom
- back
Design: See order details
Material wetted parts
Material: See order details
Hygienic design
The surface roughness of the wetted parts made of stainless steel are executed according to EHEDG Doc.8 and ASME BPE SF3.
In case of choosing the additional feature HY, we guarantee the following surface roughness values:
Diaphragm foil: Ra ≤ 0.38 µm
Laser welds: Ra ≤ 0.76 µm
Turned parts: Ra ≤ 0.76 µm
Further versions of hygienic design upon request.
Measuring system
Sensor: Piezoresistive measuring element
System filling: Synthetic oil, free of silicon FD1, FDA listed, class USDA-H1
Accuracy
Reference cond.: per DIN EN 60770-1
TU = const. (15…25) °C
φ = const. (45...75) % r.F.
pU = const. (860...1060) mbar
UB = 24 V DC (± 3 V DC)
RB = 50 Ω, HART: 250 Ω
Ground connected
MBA = 0 bar
Calibration position: Process connection bottom: vertical
Process connection back: horizontal
Reference accuracy: see data sheet
Long-term drift: Refer to nominal range
≤ 0.1 %/year
Operational availability: < 12 s
Response time t90 at current output: for 20 Hz measuring rate: typically 120 ms
for 100 Hz measuring rate: typically 50 ms
Temperature influence, case: see data sheet
Temperature-influence process-connection: Depending on design
  See data sheet for detailed information
Active compensation of process temperatures (ATC-Technology, see General Technical Advices TA_041)
Indication
Display: - High-resolution graphic display with backlight
- 4-button operation
- Freely configurable display modes
- continuously rotatable by ± 170 (detent every 90°)
- Optional: Remote display and control unit, can be used up to 10 m away from measuring point
Configuration memory: - All parameterisation data can be copied from the device into the configuration memory in the display module. The data is permanently stored there, even in the event of power failure.
- The parameters can be transferred simply and quickly to other devices.
Output
Signal: 2-wire technology 4…20 mA
Lower limit 3.8…4 mA
Upper limit 20…21 mA
Lower alarm current < 3.6 mA
Upper alarm current > 21 mA
Current limitation 22 mA
Digital communication: HART ® protocol, version 7
  Device driver:
- EDD für SIMATIC PDM
- DTM for PACTware or compatible systems (FDT compliance)
- EDD for 375 / 475 Field Communicator
Function: Adjustable:
- Linear
- Inverse response
- By square root
- Table function with up to 64 support points
Turndown: Max. 100:1
Damping: 0…999.9 s selectable in steps of 0.1 s
Measuring rate: 20 Hz, switchable to 100 Hz
Resolution: 1 µA
Current sensing func.: 3.55…21.5 mA selectable in steps of 0.001 mA
Load RB: RB ≤ (UV-12V DC)/0.022 A [Ohm]
UV = supply voltage
for HART communication: RB ≥ 230 Ω
Supply voltage
Functional range: 12…30 V DC, protected against polarity reversal
Ripple: < 5 %
Temperature ranges
Ambient: -40…80 °C
(Display visibility is limited at temperatures below - 30 °C)
Media: 20…160° C
at Ta = max. 70 °C , > 500 mbar abs with temperature decoupler up to 200 °C
Ta = ambient temperature
  Vacuum application:
10…500 mbar abs: -20…120 °C
< 10 mbar abs upon request
Storage: -40…80 °C
Tests and certificates
See documents
Type series
CI4110, CI4113

Documents

Name
Description
EN
DE
  • D4-016-2

    Data Sheet

  • BA_072

    Operating Instruction

  • XA_010

    Ex Instructions

  • XA_011

    Ex Instructions

  • SA_001

    SIL Instructions

  • ZER_090

    Certificate - ATEX

  • ZER_091

    Certificate - IECEx

  • KE_042

    Declaration of Conformity

  • Software

    PASCAL Ci4 HART (DD/EDD) for Simatic PDM V6.0 SP5, V8.1 and V9.x

  • Software

    PASCAL Ci4 HART (DTM) for Pactware

  • Software

    PASCAL Ci4 HART (DD/EDD) for Simatic PDM V9.x

  • Software

    PASCAL Ci4 HART (DD/EDD) for Emerson Handheld Communicator 375 / 475