Pressure transmitter UNIVERSAL CA for diaphragm seal operation

Type series CA2110

  • EHEDG
Pressure transmitter UNIVERSAL CA for diaphragm seal operation - CA2110

Features

  • Universal pressure transmitter, hygienic design per EHEDG, FDA and GMP
  • Stainless steel case, degree of protection IP 65
  • Direct ventilated sensor element
  • Measuring range: 0…100 mbar to 0…40 bar rel.; 0…1 bar to 0…6 bar abs.
  • Accuracy ≤ 0.2 %
  • Output signal 4…20 mA , 2-wire technology
  • Easy zero setting by using a magnet
  • Various process connections with flush mounted diaphragm, selected connections with EHEDG certificate

Options

  • Certificate of measuring equipment for Russian Federation
  • Material certificate as per EN 10204-3.1
  • Calibration certificate as per EN 10204-3.1
  • Roughness height rating with inspection certificate acc. to EN 10204-3.1
  • Wetted parts electropolished
  • Degree of protection IP 67
  • Hygienic design
  • EAC declaration (upon request)

Technical Data

Constructional design / case
Design: Hygienic case design
  Excellent moisture protection
  Fully encapsulated electronics unit
Material: Stainless steel mat.-no. 1.4301 (304)
Degree of protection: IP 65 per EN 60529
  Optional IP 67 per EN 60529
Pressure compensation: Aeration via sintered filter
El. connection: Circular connector M12x1
  Right angle plug EN 175301-803-A (DIN 43650 model A)
  others upon request
Climatic category: DIN EN 60721 3-4, 4K4H
Process connection
Design: See order details
Hygienic design
The surface roughness of the wetted parts made of stainless steel are executed according to EHEDG Doc.8 and ASME BPE SF3.
In case of choosing the additional feature HY, we guarantee the following surface roughness values:
Diaphragm foil: Ra ≤ 0.38 µm
Laser welds: Ra ≤ 0.76 µm
Turned parts: Ra ≤ 0.76 µm
Further versions of hygienic design upon request
Measuring system
Sensor: Piezoresistive measuring element
System filling: Synthetic oil, free of silicon FD1, FDA listed, class USDA-H1
Measuring ranges / overload limits
Measuring ranges / overload limits: See order details
Vacuum tightness: Long term vacuum measurements at relative measurement ranges can alter the device characteristics.
(piezoresistive measuring system, only)
Zero settings:
Zero point: Easy zero setting max. ± 20 %.
Accuracy
Limit point setting: pern DIN 16086
Accuracy (Lin./Hyst./Repr.): 0.2 % v. of mr (mr ≥ 250 mbar) 0.5 mbar (mr < 250 mbar)
Long-term drift: ≤ 0.1 % / year per EN 61298-1
Temperature influence: Range: 0…50 °C:
≤ 0.25 % of mr (mr ≥ 400 mbar)
≤ 0.4 % of mr (mr < 400 mbar)
≤ 0.5 % of mr (mr < 160 mbar)
  Range: -20…0 and 50…85 °C:
≤ 0.4 % of mr (mr ≥ 400 mbar)
≤ 0.6 % of mr (mr < 400 mbar)
≤ 0.8 % of mr (mr < 160 mbar)
  Process connection: (zero error)
DN 25/1“ 4.8 mbar/10K
DN 32/1 ½“ 2.3 mbar/10K
DN 40 1.6 mbar/10K
DN 50/2“ 0.6 mbar/10K
  (mr = measuring range)
Output
Signal: 4…20 mA in 2-wire technology
Sampling rate: 10 measurement/second
Current range: 3.8…20.8 mA
Resolution: 2 µA
Current limitation: ≤ 22 mA
Alarm state: < 3.6 mA
Load, RB: RB ≤ (UV-9V)/0.022A [Ohm]
  (UV = supply voltage)
Supply voltage
Function range: 9...30 V DC
Temperature ranges
Ambient: -20…85 °C
Medium: -20…125° C, short term 140 °C, optional up to 160 °C for 1 h.
Higher process temperatures upon request
Storage: -40…85 °C
Tests and certificates
See documents
Mounting information
Mounting position: At choice
Calibration position: Vertical
Type series
CA2110