Digital transmitter for temperature IO-Link, for resistance thermometers

Type series PA2530

Digital transmitter for temperature IO-Link, for resistance thermometers - PA2530

Features

  • Digital transmitter for temperature with IO-Link V1.1 output signal
  • Data transmission rate COM 3 (230.4 kBaud)
  • Accuracy ≤ 0.1 %
  • Input Pt100 per EN 60751
  • Nominal range -50...260 °C
  • 2 switching outputs maximum

Options

Technical Data

Constructional design case
Design: Hygienic case design
Material: Stainless steel mat.-no. 1.4301 (304)
Degree of protection per EN 60529: IP 66
Electrical connection: Circular connector M12 (4 pin)
Input
Sensor type: Pt100 per EN 60751
Characteristic curve: temperature linear
Connection type: 4-wire technology
Measuring current: ≤ 500 μA
Measuring rate: 6 Hz
Output
Accuracy: ≤ ± 0.1 %, referred to nominal range
Temperature influence ambient: ≤ 0.0025 %/K referred to nominal range and adjustment point (25 °C ± 5 K)
Signal: IO-Link device 1.1 (downward compatible to V 1.0)
Data transfer rate COM 3 (230.4 kBaud)
Min. cycle time: 2 ms
  1 switching output
  Optional: 2 switching outputs
Properties switching output:  
Switching functions configurable: - Hysteresis function or frame function
- Normally closed or normally opened contact
- Output PNP/High-side or NPN/Low-side
Switching current: ≤ 100 mA per output
Voltage drop at switching transistor: ≤ 2 V
Short-circuit proof: yes (locked)
Reverse polarity protected: yes
Current limit: yes
Hysteresis for hysteresis function: configurable
Hysteresis for frame function: Fixed settings (symmetrical; ± 0.25 % of the measuring range)
Switch-on, switch-off delay: 0.00 to 100.00 s
Supply voltage
Functional area IO-Link: 18…32 V DC *
Functional area 2 output signals: 9.6...32 V DC *
Nominal voltage: 24 V DC
* The auxiliary energy of the pressure sensor must meet SELV requirements; optionally, an energy-limited current circuit according to section 9.3 of EN 610610-1 and UL 61010-1 can be used.
Current consumption:
In idle mode: ≤ 12 mA (at nominal voltage)
IO-Link: ≤ 20 mA (at nominal voltage)
2 switching output: ≤ 200 mA (at nominal voltage)
Temperature ranges
Ambient: -40...85 °C
Media: -50…260 °C *
Storage: -40…85 °C
* Depends on used resistance thermometer.
Tests and certificates
See documents.
Type series
PA2530

Documents

Name
Description
EN
DE
  • T4-084

    Data sheet

  • BA_083

    Operating Instruction

  • HE_140

    Manufacturers Declaration IO-Link

  • KE_051

    Declaration of Conformity