Pressure transmitter UNIVERSAL CA for diaphragm seal operation

Type series CA2110

  • EHEDG
Pressure transmitter UNIVERSAL CA for diaphragm seal operation - CA2110

Features

  • Universal pressure transmitter, hygienic design per EHEDG, FDA and GMP
  • Stainless steel case, degree of protection IP 65
  • Direct ventilated sensor element
  • Measuring range: 0…100 mbar to 0…40 bar rel.; 0…1 bar to 0…6 bar abs.
  • Accuracy ≤ 0.2 %
  • Output signal 4…20 mA , 2-wire technology
  • Easy zero setting by using a magnet
  • Various process connections with flush mounted diaphragm, selected connections with EHEDG certificate

Options

  • Certificate of measuring equipment for Russian Federation
  • Material certificate as per EN 10204-3.1
  • Calibration certificate as per EN 10204-3.1
  • Roughness height rating with inspection certificate acc. to EN 10204-3.1
  • Wetted parts electropolished
  • Degree of protection IP 67
  • Hygienic design
  • EAC declaration (upon request)

Technical Data

Constructional design / case
Design: Hygienic case design
  Excellent moisture protection
  Fully encapsulated electronics unit
Material: Stainless steel mat.-no. 1.4301 (304)
Degree of protection: IP 65 per EN 60529
  Optional IP 67 per EN 60529
Pressure compensation: Aeration via sintered filter
El. connection: Circular connector M12x1
  Right angle plug EN 175301-803-A (DIN 43650 model A)
  others upon request
Climatic category: DIN EN 60721 3-4, 4K4H
Process connection
Design: See order details
Hygienic design
The surface roughness of the wetted parts made of stain-less steel are executed according to EHEDG Doc.8 and ASME BPE SF3.
In case of choosing the additional feature HY, we guarantee the following surface roughness values:
Diaphragm foil: Ra ≤ 0.38 µm
Laser welds: Ra ≤ 0.76 µm
Turned parts: Ra ≤ 0.76 µm
Further versions of hygienic design upon request.
Measuring system
Sensor: Piezoresistive measuring element
System filling: Synthetic oil, free of silicon FD1, FDA listed, class USDA-H1
Measuring ranges / overload limits
Measuring ranges / overload limits: See order details
Vacuum tightness: Long term vacuum measurements at relative measurement ranges can alter the device characteristics.
(piezoresistive measuring system, only)
Zero settings:
Zero point: Easy zero setting max. ± 20 %.
Accuracy
Limit point setting: pern DIN 16086
Accuracy (Lin./Hyst./Repr.): 0.2 % v. of mr (mr ≥ 250 mbar) 0.5 mbar (mr < 250 mbar)
Long-term drift: ≤ 0.1 % / year per EN 61298-1
Temperature influence: Range: 0…50 °C:
≤ 0.25 % of mr (mr ≥ 400 mbar)
≤ 0.4 % of mr (mr < 400 mbar)
≤ 0.5 % of mr (mr < 160 mbar)
  Range: -20…0 and 50…85 °C:
≤ 0.4 % of mr (mr ≥ 400 mbar)
≤ 0.6 % of mr (mr < 400 mbar)
≤ 0.8 % of mr (mr < 160 mbar)
  Process connection: (zero error)
DN 25/1“ 4.8 mbar/10K
DN 32/1 ½“ 2.3 mbar/10K
DN 40 1.6 mbar/10K
DN 50/2“ 0.6 mbar/10K
  (mr = measuring range)
Output
Signal: 4…20 mA in 2-wire technology
Sampling rate: 10 measurement/second
Current range: 3.8…20.8 mA
Resolution: 2 µA
Current limitation: ≤ 22 mA
Alarm state: < 3.6 mA
Load, RB: RB ≤ (UV-9V)/0.022A [Ohm]
  (UV = supply voltage)
Supply voltage
Function range: 9...30 V DC
Temperature ranges
Ambient: -20…85 °C
Medium: -20…125° C, short term 140 °C, optional up to 160 °C for 1 h.
Higher process temperatures upon request
Storage: -40…85 °C
Tests and certificates
See documents
Mounting information
Mounting position: At choice
Calibration position: Vertical
Type series
CA2110